Key Points For Selecting The Support Structure Of Constant Voltage Transformer
The distance between the equipment and the wall should conform to the design drawings and specifications, generally with a lateral distance of not less than 800mm and a distance from the door of not less than 1000mm, with an allowable error range controlled within ±25mm. For the 3 phase constant voltage transformer equipped with a gas relay, the top cover needs to be sloped at a 1% to 1.5% angle along the airflow direction to ensure the normal operation of the gas monitoring device.
The material selection for the support platform must consider long-term load factors. Steel components should be free of obvious rust, and all connecting bolts, except for anchor bolts, should be galvanized, equipped with appropriate size flat washers and spring washers. During hoisting of unit constant voltage transformer for home, the rigging must meet safety standards, the wire rope should be fixed to the dedicated hook position for the oil tank, and the hoisting process should be kept stable to avoid impact and vibration damage to the internal structure.