Solution To Dynamic Voltage Regulator Failure
The following are some reasons for the Dynamic Voltage Regulator (DVR) fault phenomenon and treatment methods
Fault phenomenon: cannot start
Reason: input wiring is unreliable; no input voltage
Handling method: rewire and check whether there is any broken wire; use a voltmeter to measure whether there is voltage in the input wiring. Fault phenomenon: no voltage indication in a certain phase
Reason: the wiring of the terminal corresponding to the phase is unreliable
Handling method Check the connection status of the phase wiring and use a multimeter to measure whether there is a circuit break
High power detection
Fault phenomenon: After the dynamic voltage stabilizer is started, the voltage of each phase is unbalanced, and it is too high or too low
Reason: Abnormal input voltage; input and output lines are connected in reverse; each phase does not work properly; input neutral line is not connected or wiring is unreliable. Solution: Check whether the power grid is normal; check the wiring and correct it; check whether the connection of each connector is loose; connect the neutral line (if the neutral line is not connected, when adjusting the output voltage of a certain phase, the voltage of another phase will also change accordingly
Fault phenomenon: The voltmeter on the panel indicates that the voltage of each line is seriously unbalanced
Reason: The voltage of each phase of the power grid exceeds its voltage regulation range; the load is seriously asymmetric
Solution: Loads with high requirements for three-phase balance, such as three-phase motors, must be shut down and the power grid must be checked; adjust each load to ensure the balance of each phase as much as possible.